![]() |
|
Low Refrigerant in Capillary Tube system
1.
New AB lost some refrigerant
2.
New AB Leaks
Refrigerant maybe inside Power Plate.
3.
AB low on refrigerant and
poor performance
6.
Correction to misleading
information
7. BD50 kit put together from Parts
DIY Refrigerant Problems
8.
Non Destructive testing analysis Low
on Refrigerant
9.
BD35 Performance Question Refrigerant Low
on refrigerant
10.
Adler Barbour Problems need
recharge Low on Refrigerant
11.
BD50 Refrigerant Charge For Adler Barbour with Power Plate
Refrigerant Low
1. New AB lost some refrigerant
Richard, I just purchased
your 12 and 24 volt refrigeration manual and it is extremely helpful. The
catalyst for buying the manual was to get better insight in case I need to
recharge my Adler Barbour Cold Machine. When I was assembling it, the
refrigerant was lost. Know that I have the book I can run some test to see if a
charge is needed. If so, I need some additional clarification on how the
connection is made to the low pressure side of the compressor. It currently has
a cap, once the cap is undone, without the compressor turned on, will any
refrigerant be loss?
2. New AB Leaks
Refrigerant maybe inside Power Plate.
Add refrigerant and leak test. If soldering is required, flow nitrogen through tubing to
prevent formation of oxides in tubing Repair leak Replace filter/dryer Leak test again Vacuum air, gas and moisture from system Service with correct amount of 134a refrigerant Leak test again
Answer
3.
AB low on refrigerant and poor performance First, let me
thank you for your help. This website and your book have proved invaluable to
all of us that own boats with refrigeration. Now this is the update on what
has/is occurring. I purchased the A/B Super-Cold Machine. When initially
installed, the box/evaporator had a temp of 18˚. The bottom of the refrigerator
was 38˚ and the top was a little high at 50-52˚. Per your book I added a small
fan with hose attached to circulate the air, with a result of the top now having
a temp of 42˚. The thermostat that came with the unit has a 680 ohm resistor so
the compressor is running at 3000 rpm. It is set at its upper limit to achieve
these temps. The evaporator seems to have frosted over except for one corner in
the back. This section is about 6 inches wide from the top to the bottom of the
evaporator. Is this possibly a low freon problem or is it something more
serious?
Answer:
It does sound like your refrigerator system is slightly low on refrigerant for a
13 cu. ft box. I hope you purchased the large 15 inch bin evaporator. With the
thermostat set to full cold does the compressor cycle off and on more than twice
per hour? How long is a compressor cycle from start to the next start? Do you
have an amp-hr meter like the Link meter? Where do you plan to cruise in the
future? Are you satisfied with the temperatures you are getting in the box now?
What is your approximate location? A 13 cu. ft. box with a BD50 compressor
running at 3000 rpm, drawing only 4.7 amps and an area of the evaporator without
frost does indicate a loss of refrigerant. Boaters who have installed Adler
Barbour units have had this problem since Adler Barbour switched to the self
piercing line connectors. There is an O ring in the connector that is designed
to retain the pre-charged refrigerant while the self piercing disc is broken.
When metal to metal contact is made between the male and female parts of the
coupling the O ring becomes redundant. If special attention isn’t paid to the
coupling alignment and follow up tightening of the coupling nut refrigerant can
be lost.
Reply:
Once it is
determined that there is a small loss of refrigerant and it has effected the
system’s performance what do you do? The unit is under warranty but I am told
that Adler Barbour won’t cover loss of refrigerant at installation, because the
line couplers were installed incorrectly. Now the real catch 22, these days
where are you going to find someone knowledgeable in servicing one of these
small capillary tube systems?
Reply:
Richard, the evaporator that we purchased is the
VD-152...largest vertical evap that they sell. With the thermostat set to full
cold, the compressor (monitored for 30 minutes) seems to cycle on and off every
5 to 6 minutes. For instance, at 0:00 on, 0:06 off, 0:10 on, 0:16 off, etc...I
do not have an amp hr meter yet. Cruising grounds will be the tropics. I would
prefer that it was a little colder but I can live with it at the moment. The
boat is located in I am assuming
from your questions that the cycling on off every 5 minutes is not normal. Could
it be the low refrigerant level? Will it do damage to the system?
Answer:
This quick cycling is not very efficient but it will
not hurt the compressor. Now the task is
to lower the box temperature and maybe change the compressor duty cycle to 15
minutes ON and 15 minutes OFF at the lowest possible compressor speed to achieve
the System’s Optimum Coefficient of Performance (SCOP). Nice words but what you
really want is to have a good refrigerator consuming the least amount of amp-hrs
per day. The base line
that you have recorded indicates that the capacity of the compressor is greater
than the ability of the evaporator to absorb heat. This condition can be caused
by:
·
Low on
refrigerant
·
Thermostat
aluminum capillary tube touching the evaporator somewhere along the evaporator.
This tube, for correct thermostat calibration, must touch only in a single U
shape under the plate designed for it.
·
Insufficient
air movement over the evaporator. Because the box
is so large and the boat will operate in tropical climates, the compressor will
need to run some days at mid day at 3500 rpm. Hopefully at slower more efficient
speeds when the sun is off the boat.
A fixed or manual compressor speed change is not practical under these
conditions as the box is too large. Your refrigerated box is twice the size that
I recommend in my book to be refrigerated by a BD50 compressor in the tropics.
When you are in really hot weather the compressor may need to run 24 hours a day
at 3500 RPM. Danfoss does
offer an automatic speed control included in two of their modules along with a
module fan that they require on BD50 Compressors which run at 3500 rpm. Currently none
of the boat refrigeration manufacturers offer the new Adaptive Energy
Optimization (AEO) module. So the next best thing is to purchase Frigoboat’s SSC
control and a two inch 12 volt fan from Radio Shack and installed it to cool the
module’s heat sink. Before you
install the SSC controller and after refrigerant is added run the system full
cold and check performance figures again including, Cycles, temps, and amps. If the
compressor still cycles too often and the box temps do not drop properly an
additional fan in the box may be required. Recently I
installed a cold machine which I purchased about three years ago (BD50F w/large
vert. evap.) When set at 4-5 for 12 hours, only part of the evap frosts over,
and ice tray does not freeze when in contact with inside wall (as per
instructions). I realize that this is likely due to inadequate 134a charge, but
is it possible on a new install (i.e. could the tubing set have lost charged
sitting in the box) or is it possible that the metal diaphragm piercing
connectors leaked during the install. I have a manifold gauge set which I will
hook up this weekend and check the low side pressure. Is there also a
possibility that my condenser is partially blocked? (metal particles from the
piercing valve if I over-torqued it?). If so will evacuating the system help?
Answer: This is the
fourth time I have heard of this problem with Adler Barbour refrigeration units.
The first one I was asked to check and service, AB paid the owner for my service
call. I understand they no longer pay for servicing new units as they feel the
installer caused the refrigerant to leak out when screwing the connections
together. Newer model connectors are of a design used for years in
pre-charged air conditioning systems and I know of no problems from a broken
diaphragm causing problems. When these connectors are connected by hand, an O
ring first comes in contact and is intended to seal the refrigerant in until the
tightening process is complete. The final wrench tightening will complete a
metal to metal lifetime seal. Yes there is a lot of other problem area you can dream up
that could cause this but they are not indicated by the results you are seeing.
Frost level is low indicating low refrigerant. Things to remember before connecting gauges and servicing: 1. Purge refrigerant through gauge set to remove air and
moisture. 2. Stop compressor before connecting gauges, as it may be
running in a vacuum. 3. Everything in the system including the ice box needs to be
70˚ F. or above. After the compressor is started the suction pressure will
drop and stabilize this may take 10 minutes. Then warm the box, A setting of 6
to 8 psi would be the correct charge for 134a refrigerant. If at 10 to 20
minutes this pressure is low, add a small amount of refrigerant. Yes small
amount, and then wait till it seeks a new stabilized pressure before adding
more. If the system wad over charged, and yours is not, the pressure would be
higher than 10 psi. The exception to these pressures would be if you have AB’s
large 15 inch evaporator then the pressures should be 2 psi higher. A small
overcharge of ½ ounce or more (15 Grams)of refrigerant will cause an increase of
daily amp-hrs used. If you are unable to adjust the
refrigerant level in the first 20 minutes, stop and let the evaporator warm back
up to 70˚F.
After 20 minutes, the suction pressure will automatically
adjust down to lower temperatures and lower flows as the plate and box cools.
Use pressures for servicing only in a time window between 10 and 20 minutes with
a warm box. Fine tuning later is done by setting frost line (upper heat),
confining it to evaporator. After removing the gauge set be sure to replace the sealing
cap with its seal still inside on the service fitting. Common slow refrigerant
leaks are caused by poor sealing of these caps.
Slow leak
Reported by Captain and helpful or unhelpful tips
from others.
Sheesh! people. It's a
Danfoss sealed compressor with one service port on the
As for leak detection, no doubt an expensive gadget does
the job better than
Answer:
I will only reply once to this misleading game. Stay with the facts you have and
forget the misleading information you read and hear from these hopefully well
intended helpers. Your
small refrigeration unit failed to cool enough to form frost over the complete
evaporator after the system shut down for a long period. I believe I advised you
that there are three likely areas where leaks are common on your unit. 1.
Line tube connectors, 2.servicing cap seal and 3. very small corrosion
holes in the aluminum evaporator. Because your unit contains 85 to 120 grams of
134a refrigerant and from your description of frosted areas my guess was,
refrigerant loss was 1 to 2 ounces. With this amount of loss and the time it
took to leak out standard leak testing equipment might not find the leak. A
competent technician might need to make more than one service call to confirm
the leak using a two step 6. Correction to misleading information: Capillary tubing mechanical clogging is very unlikely and
maybe less than one in a thousand performance problems are caused by material
blocking cap tube. When there is moisture freezing in cap tube, a plate
temperature is maintained at 33˚due to freezing and thawing with no frost. If a
cap tube is mechanically blocked, shaking it will not open the blocked area. Your system when running should never see suction pressure
over 10 psi and that is 10 minutes after start up with a 100 degree box
temperature. Very few technicians have time enough and experience to service
your unit in the field as accurately as you can. Hearing
the hissing noise caused by refrigerant leaving cap tube is only an indication
that there is refrigerant and oil being pumped and nothing more unless you have
Superman’s ears. After adding refrigerant your evaporator frosted properly but
there is still a leak so your problem will return again. DIY leak testing information I gave you before is done with
compressor turned off. The secret in this process is to agitate the mixture on
leak test area until the liquid surface tension against test area is achieved. Mix up a small amount of dishwashing liquid soap and water
50/50 mixture to apply with a one inch paint brush. With 134a refrigerant bottle
in upright position (Gas Only), compressor off, allow system pressure to
increase to 30 to 50 psi and quickly feel with your hand for a leak. If there is
a bad leak you can feel and hear it change as your fingers pass over it. If you
did not find a leak add more gas until pressure stops rising. Now begin liquid
foam tests.
Painting this mixture on a suspected leak area will not find a
leak. Using the brush to agitate mixture into a shaving cream
like mixture on a suspect area and sitting back watching the
spot for a couple minutes will find the smallest leak if there
is one.
7. BD50
kit put together from Parts DIY Refrigerant
Problems I installed a BD50 w/AEO module, air-cooled condenser, large
evaporator plate system (parts from RParts) about 6 months ago, in a 9cu.ft.
icebox with 4in of blueboard insulation (also rebuilt). I pressure tested it
before charging: it held 150lbs of pressure for 3 days without noticeable
change.
As of three days ago it was staying cold just fine; three
months ago I measured the duty cycle to be 20% (to maintain icebox temp
~36degreesF in an ambient 60degree environment, lightly filled with foodstuffs).
I hadn't paid close attention since I measured the duty cycle, but I have a
green LED next to the icebox to tell me the compressor is running, and the red
fault LED also in eyesight. The compressor seemed to be running a normal amount
for the past few weeks, and there was no action on the red LED. The past two days I had the icebox turned off so I could
install shelving for organization. I turned it back on last night and the
compressor ran 12 straight hours to get the fridge down to temperature (from 60F
to 38F)--there is not much food in the icebox either. Only 1/8th of the
evaporator plate frosted over (and stayed that way for the duration of the 12
hours the compressor ran). It appears to be the first 1/8th of the tubing after
the capillary tube.
Could I have damaged the evaporator plate during my
construction project? Could this be a symptom of a damaged plate? Or perhaps I
did not notice the condition before the past few days, and my recent project
drew attention to it? If it weren't for the construction project, I would
suspect insufficient refrigerant, caused by a slow leak somewhere, which I did
not find during my installation. But wouldn't I have noticed that last week
(before my project)? Would the green LED have been on all the time (it
definitely wasn't running more than 50% of the time). Boy, I really REALLY hope
I didn't damage the plate. I tried to be so extremely careful. I will be really
depressed if that ends up being the problem.
Answer: One area I like
to remind people of is that if capillary tube system is serviced with a warm
ambient temperature and then operated at a low ambient cooling medium
performance will be degraded and frost area will be reduced. I do not believe
that reduction of 80% frost area in this case is causing your problem. A very slow leak in low pressure side of system would have
been detected 6 months ago with the three day test. The question now is the loss
of refrigerant did a micro leak develop over time or was it a new leak due to a
very small hole caused by working on the box’s interior. Sometimes leaks are caused by not using special refrigerant
flare nuts. Light weight hardware store nuts tend to expend at a different rate
as temperature changes causing leaks. Many times failure to use servicing
fitting caps with a seal inside can cause small leaks. If refrigerant loss was
slow over time when in operation evaporator frost coverage would slowly be
reduced beginning with a small area. I have seen a frosted area reduced to 50%
in six weeks and when system is off a few days all refrigerant is lost. When
system is not running the low pressure side of system is the same as high side. If the evaporator prior to the three day shelf work, had
frost covering 90% of its surface and now is only 20% I would suspect you
damaged the evaporator plate. The only recommendation I can give you is to add refrigerant in small amounts till frost covers 80 to 90% of evaporator. Then stop compressor and test for leaks at all connections with a mixture of 50/50 liquid soap and water. It is important to use a one inch paint brush against test area forcing mixture into a shaving cream texture. This method of leak testing is slow, one fitting at a time, but it will find leaks as small as ½ an ounce a year. Leaks in aluminum evaporators are very hard to find and are not repairable. If you drilled any new mounting holes in evaporator I would check them first. Again pressure in low side of system when unit is running will be less than 8 psi so leak testing is best done with warm box and system turned off .
Reply:
WOW am I glad you exist on the
internet, thank you so much for the advice. That is great to know, that leaks in
the low pressure side can be masked until the system is shut down
entirely--makes complete sense but I had never thought of it.
Answer:
If it loses its charge
rapidly, then you will have strong evidence that a hole in the evaporator plate
is the culprit. Additionally, if the leak is that large, you should be able to
see the UV dye with the blacklight. If after two days it is still running
strong, with no evident signs of leaks with the blacklight, then you have good
evidence that the leak was a long slow one, and you will need to test each
fitting with the soap/water mixture.
Reply:
I have your book; it convinced
me of the futility of attempting to repair any holes in the evap. plate, so if
that is the culprit I will replace it. If there is a slow leak, over time it draws in moisture that contaminates the system, correct? So it can probably be recharged a few times, but in the end moisture will be sucked in through the hole in the low side and clog the capillary tube, at which point a full "reboot" (leak repair, vaccumed to remove moisture, filter/drier replaced) will need to happen anyway, right? Any sense of how long it takes for the moisture to contaminate the system through a slow leak?
2) Unfortunately,
and to my immense annoyance, I cannot recall what the duty cycle or frost
pattern was prior to messing around in the icebox two days ago. I know that it
wasn't 100% duty cycle just from vaguely paying attention to the compressor
running, but I have no information beyond that. I rack my memory for clues,
without success.
3) I used all
refrigeration flare fittings from RParts in the system construction (it was
their 1M kit).
4) I used a gauge set with good o-ring seals to originally
charge it.
Answer:
Refrigerant charge on a system using
a capillary tube flow control device must be correct or performance will be
degraded. As the condenser’s cooling medium, in your case air, changes
temperature the pressure and temperature of refrigerant leaving condenser will
upset the equilibrium of the liquid and vapor passing through the capillary
tube. Factory charged refrigerators are generally charged with a fixed volume of
refrigerant by weight based on standard day cooling medium temperatures. When
these small cap tube systems are field serviced on a boat in the north to
correct evaporator superheat and then transit south to the tropics evaporator
super heat will be low causing frost to extend beyond evaporator. In you case
going from warm to cold condenser cooling medium would reduce the frost area on
the evaporator. I do not believe that initial low refrigerant is the only cause
of your problem, so add refrigerant and leak test.
Reply:
One more thing--perhaps I am
overlooking an obvious answer, but how does one add just a few drops of UV dye
to an already charged system?
Answer:
To insert dye you must solve two problems first: Find some of the Dye can be added to the blue hose of the servicing gauge set.
Begin with both red and blue gauge valves closed. Connect refrigerant bottle to
yellow hose. With blue hose held vertical open blue valve and purge refrigerant
through gauge set out through blue hose, then close blue valve. Refrigerant is
heavier than air so keep blue hose vertical while adding dye. Connect blue hose
to low pressure side of compressor. Turn refrigerant bottle upside down so that
liquid refrigerant will flush dye into system. Open blue valve for 5 seconds
then close valve and turn refrigerant bottle with gas only side up. Wait several
minutes before starting compressor so that liquid refrigerant will have returned
to gas in compressor. Service with refrigerant adding small amounts and then
wait till low pressure stabilizes before adding more. Run system a few days to
mix dye with oil. If evaporator stays covered with frost then turn compressor
off for three days. When frost line on evaporator no longer covers 90% of
evaporator, use black light to find leak.
Reply: Should
I add any oil while I'm doing this? I now have a small container of the UV dye
(in a plastic bottle with screw-top cap, unpressurized).
To confirm: So I put the flare union on the end of the blue
hose (the end that attaches to the service fitting), hold it vertical in my
hand, and purge it. I continue to hold it vertical to prevent air from entering,
and then I add 15 drops of the UV dye into the flare union, letting it drain
down into the hose. Then I remove the flare union, and gently move the end of
the blue service hose down to screw it onto the service fitting--this would be
when I am most worried about air slipping into the system, as I am moving the
hose and screwing it onto the horizontal service fitting. I leave the service
fitting closed to the gauge set while doing this. Then I hold the refrigerant can above the level of the gauge
set, and invert it. (blue valve closed). Liquid refrigerant piles up against the
blue valve, then I open the blue valve for five seconds and then close it.
Liquid refrigerant piles up against the service fitting, then I open the service
fitting and the liquid refrigerant enters the system, flushing the dye out of
the hose and into the system with it. Then I wait a few minutes for all the
liquid refrigerant to boil off in the system (thereby avoiding liquid slugging
of the compressor). Then I start the compressor and service with additional
refrigerant as necessary to obtain a 100% frost pattern on the evaporator. Then I put everything away and wait until it is apparent that
some refrigerant must be leaking away, however many days or weeks that may take,
and it will be evidenced by a diminished frost pattern on the evaporator.
Then
I take out my glasses and blacklight
and go searching. Did I get all that right? And the minute amount of air that
slips into the hose as I'm screwing it onto the service fitting is acceptable,
I'm supposing, since this is how you're saying it is supposed to be done. This
is pretty cool stuff. And I'm pretty excited that I'm learning how to do it all
myself.
Answer: You are on the
right track. When adding liquid refrigerant the bottle does not need to be
higher than gauge set just upside down. After removing ¼ union I put my finger over end of hose until
connection to unit is made. You may want to use a syringe needle to add dye to
hose as gas bubbles will be coming out as oil goes in. Once hose is connected open three way suction servicing valve
halfway then open blue gauge valve for five seconds. With both valves open at
the same time liquid will flow into unit taking dye with it.
Reply:
Ok, I hooked up the gauge set to check the operating
pressures, before doing anything else, and when I saw that the suction side was
pulling somewhat of a vacuum, I decided to modify the plan.
I was thinking
that there was potential for air (maybe moisture) to have entered the system if
the leak was on the suction side. Also, when I went to the refrigeration supply,
they were having a sale on a vacuum pump, so I bought it. Then I borrowed a
guy's micron vacuum gauge from down the dock, and vacuumed down to 450 microns,
and closed off the system. Within 20 minutes it had risen to 520 microns,
confirming a leak. So I let the system equalize with ambient pressure, then
added 15 drops of UV dye to the gauge, set the suction side hose into the end
with the male-male flare union as you described. Then I vacuumed down the system
to 450 microns and charged with refrigerant. Now I am waiting for leak to
present itself. I have doubts
that the amount of UV dye will be successful in identifying the leak: I
overcharged very slightly at first, and bled off a tiny amount of refrigerant
from the connection at the flare fitting. Only then did I realize my mistake: I
probably released UV dye onto the area, reducing my ability to identify the
leak. So I put on the glasses and looked around with the light and couldn't see
anything at all. This causes me to doubt the effectiveness of it showing a leak.
Though perhaps, after it runs for a few days, the dye will have mixed better
with the refrigerant. The dye seems to
dry/stick to surfaces, though, so perhaps most of the dye ended up painting the
inside of the blue hose on my gauge set, and very little made it into the
system. I don't know, and for now I'm not going to stress out about it. We
depart for Thank you very
much for your excellent advice and patient explanations. Your book has been very
helpful to me in gaining an intuition about the various specialized problems
that may arise in our small boat systems, and the corresponding approaches to
fixing said problems. Above and beyond the book, this forum and your responses
to my questions have tripled my refrigeration knowledge (albeit not very large
to begin with!), and it brings me happiness to be able to learn and understand
how to take care of these things for myself. You have my gratitude! Answer: A 30 micron change in 20 minutes I would believe is normal as trapped liquid moisture is being phase changed to gas. When 12,000 microns of vacuum is equal to one inch of vacuum gauge indicated vacuum a 30 micron change does not prove there is a leak. If system was vacuumed for four hours with system’s ambient temperature of at least 100˚F and vacuum reduced to 5,000 microns in 20 minutes then somewhere something is leaking and it may even be the servicing gauge set or its hoses.
Ten drops of dye is sufficient for your system. The leak you
have, if there is one, is a micro size leak and will not display
visible dye for many days with system running or when frost area
coverage of evaporator is reduced by 50%.
8. Non
Destructive testing analysis Low on Refrigerant I am about to re-gas my
system with 134A, but…. How do you know how much gas to put in? Everything still
works, BUT I think it should be colder. I don't have pressure gauges (yet) so I
will confirm what is happening on that side of things soon. I also need to check
the temp in the cool box. To prove I've done my homework the answer to my
question was high pressure 110 psi. and low pressure range between 5 and 10 psi,
however, let everything run for at least 10 mins to settle down.
Answer:
Experience proves a boat captain needs to be smarter at analysis of refrigerator
problems than a so called refrigerator service technician because no two systems
have the same problems. Your suggested approach to locating a problem is a-round
about service tech’s approach to be able to charge customer more money. The
decision that refrigerant needs re-gas or connecting gauges is premature and may
guide you in the wrong direction wasted hours of system down tine while doing
destructive testing. In this case you know
cooling performance inside box is not what it should be. Looking for unusual
temperatures throughout refrigerant cycle by non destructive ways may be all
that is needed to pinpoint the problem. Compressor compresses refrigerant vapor
and high pressure gas gets warm due to compression and sent to condenser where
most of heat is removed. Gas when leaving condenser is cool to a warm high
pressure liquid and filtered on its way to refrigerant flow control device, in
this case a long orifice capillary tube, the only major restriction to
refrigerant flow in this complete system. After flowing through capillary tube
high pressure and now high velocity liquid is sprayed into low pressure areas of
evaporator where it absorbs heat as it makes a phase change of liquid to a gas.
The reason refrigerant liquid must make this phase change only in evaporator is
so box cooling process occurs inside evaporator and not somewhere else in
system. Gas return line form evaporator to compressor may be cool but not
frosted.
Frost anywhere in the refrigeration loop other than at the evaporator will
indicate too much refrigerant or a restriction to flow on this cap tube system.
Too much refrigerant would be from someone
tampering with refrigerant. There are areas where there are slight restrictions
that can collect material reducing flow thus causing a cold or frosted spot such
as filter/dryer, or solder joints and refrigerant line connectors. Picture attached to your post shows a large amount of frost on what appears to be suction line connector. If this is suction line and line between it and the evaporator is not frosted, there is partial blockage inside this connector. If the line all the way to the evaporator is frosted and there is no frost on the evaporator, flow restriction is where frost starts.
9. BD35
Performance Question Refrigerant Low on
refrigerant
Last year with your book as a
reference and your answers to help, I installed a new quick connect to both my
A-B compressors- both BD3 with R134a, and recharged to a 5.5A current draw after
20 minutes with pure R134a. I never ran the freezer very much last year after recharging
so I don't have good performance data on that unit, but the refrigerator ran
much better with adequate cooling and reasonable power consumption. This spring, the initial current draw was in the 4-4.5A range
on both the refrigerator and freezer compressors. Frosting of the cold plate
seemed to take a long while also. Reviewing my data that I recorded last year at recharge, it
appeared that the low initial current and up to 20 minutes was likely due to a
slight R134a loss. I then added a very small amount of R134a to both the
refrigerator and freezer compressors being careful to purge the charging hose
each time. I added small spurts until the current draw at 20 minutes was between
5-5.5A. Now I am on a four week cruise and the power draw of these
two units seems excessive. Overnight I measure the power draw to be about 60AH
for 8 hours. The refrigerator temp is holding about 35F and the freezer temp is
between 11-19F. I think the refrigerator is running fine, but the freezer is
my concern. It seems to run for long periods even when the temp is at 11˚F. The
current draw at 11˚F is 5.2A. The thermostat setting is at 4. The inlet
connection and inlet line (about 20") are all frosted within the box. The
connection to the return suction line is frosted all the time, and occasionally
I have observed the return line (about 20") also being frosted within the box. Question:
Do these conditions indicate too much freon? Overall the total power consumption
is about 175AH per day. This seems excessive to me as I believe that the
refrigerator should be about 60AH. I would expect that the freezer would draw
more but how much more? The refrigerator is about 7.25 cu ft and the freezer is
3.5 cu ft with 3" walls. Last night I turned the thermostat to zero and the
freezer shut off. I then put it back to 3.5 and left it overnight. This morning the freezer had warmed to 24˚F from 11˚F last
night (over 9 hours) and the freezer compressor wasn't running. I tapped the
thermostat and a few minutes later the freezer compressor began to run. Is it
possible that the thermostat is "sticky" and is just causing the freezer to run
excessively? I am not familiar with thermostat failure modes.
Answer: As long as
Danfoss BD compressor runs and there is cooling you should not adjust
refrigerant volume based on amperage. Tampering with refrigerant is destructive
testing in most cases. Your unit has a capillary tube expansion device so
correct refrigerant volume is always determined by temperature of ambient air
cooling medium passing through condenser and frost area coverage on evaporator.
In cool weather there will be slightly less evaporator surface area frosted and
in hot weather there will be slightly more cooling of line outside of
refrigerator. When you have a thin plate evaporator with correct refrigerant
charge and proper condenser cooling the evaporator’s frosted area will be 90% to
100% covered and no frost on return line outside of refrigerated area. Too much
refrigerant wastes energy because the compressor cycles too often and the
cooling effort is not all in the evaporator where it should be. On this unit the thermostat is a switch
controlling the evaporator’s temperature. Its calibration depends on where and
how its sense tube is contacting the evaporator. When correctly installed,
thermostat will produce an evaporator temperature of about +12˚ F with control
knob set between 3 and 4.
Box temperature will be relative to box design and
present heat load. It is possible for thermostat to freeze up and keep
compressor running continuously if it is mounted too close to evaporator plate.
Spray inside of thermostat switch with WD40 and work knob through off position
several times. If problem reoccurs replace it.
10.
Adler Barbour Problems need recharge Low on
Refrigerant
11. BD50
Refrigerant Charge For Adler Barbour with Power
Plate
Refrigerant Low
Three amps while running is confirmation that some
refrigerant has been lost. Once you have confirmed that you have lost refrigerant, you
will need to carefully follow the steps below to solve the problem.
First leak test: Leak
testing should be done by using a 50/50 mixture of liquid soap and water. To
enhance this mixture and break down the liquid to increase surface tension a 1
inch paint brush is used to stab suspect area creating shaving cream type foam.
A slow leak may take a minute or two to show up. I know that this is tedious but
it will save you much time and aggravation in the future if it is done
correctly. Another important step will be to purge moist air out of
gauge set before connecting it to compressor. AB’s power plates now, I believe, have O ring fittings so if
a leak is found they will need to be replaced. Leak testing of power plate connection must be done with a
warm plate and compressor off. With compressor running pressure on these
fittings will always be less than 10 psi.
These are the leak testing steps to follow: •Compressor is off. •Before using gauges make sure blue gauge reads 0. If not
make a note of error. •Connect 134a container to yellow hose of gauge set. Both
valves on gauge set will be closed. Any container of 134a is OK unless this
container also has an oil charge. You do not want to add additional oil. •Do whatever you need to do to pressurize yellow hose. •Remove leak protector cover from refrigerant service port
coming out of compressor dome. •Make sure that the blue hose is connected correctly to gauge
the end with valve core depressor will be at compressor end but do not connect. •Now purge yellow and blue hoses by opening blue low pressure
gauge valve for 3 seconds close valve and NOW connect blue hose to compressor
dome service fitting. Red hose will not be used. •With refrigerant bottle upright open blue valve letting gas
refrigerant into system until pressure stops increasing on blue gauge and close
blue valve. The pressure in plate will be relative to plate temperature this is
why a warm plate is best for leak testing. A 70 plate with 134a refrigerant will
produce around 70 psi on blue gauge. •Now begin leak testing with above method defined as it will
locate ½ ounce leakage per year if done properly.
Final steps to follow when servicing with refrigerant
•Because I don’t know what resistor is
in thermostat wiring I am assuming your compressor is set to run at 3000 rpm so
lets use a base amperage of 6 amps under the following conditions, power plate
70 to 80˚F
before compressor startup •At 10 minutes after compressor startup refrigerant volume
must be adjusted very slowly to 8 to 10 psi on low pressure (Blue) gauge, at 20
minutes pressure should begin to drop as plate cools so do not add more
refrigerant based on pressure. If refrigerant is added too fast, the compressor
will shut down on overload. •After 20 minutes with 70 to 85˚ F
ambient air temp in boat and no frost on power
plate amperage should be near 6 amps if not add small amount of refrigerant. •As plate develops frost cover and continues to get colder
suction pressure will continue to drop. As suction pressure drops so will
amperage. •When connecting or removing hose connection compressor must
not running this prevent air from contaminating refrigerant. •When servicing is complete be sure to replace leak proof cap
making sure its rubber seal is still inside. |
| Email Us Forum |